Time / Date: 7/25/2023 12:43:42
|
JSP ID: 1306
|
Scope of Work: Provide LOTO procedure for contractor to change ballast lamp on one of the fume hood.
|
|
Work Order:
|
Building: Bldg. 978/Rm. 4550
|
Person in Charge: Felipe Sanchez
|
Lead / Supervisor: Other
|
Logged Email: fbsanchez@lbl.gov
|
Division: Facilities
|
QEW Level: QEW 1
|
|
Modes of Work: Mode 0 - Electrically Safe Work Condition
|
|
Second Person Requirement: Not Required
|
|
Second Person Identified:
|
|
List Other Participants:
|
|
Affected Persons Notified: N/A
|
Switching: No Switching Required
|
Panel / Equipment ID: n/a
|
System Information Review:
|
|
Control of Hazardous Energy: Simple LOTO
|
|
Equipment Condition:
|
Sequence of Job Steps
List basic sequence of steps from start to finish.
Cabinet was already shutoff upon arrival. Pulled out plug from outlet, checked voltage =118Vac. Applied LOTO hardware at power plug. Advised TSS technician that he can start troubleshooting. Ballast replaced with brand-new lamp. Technician tested equipment, working fine. Removed LOTO lock, equipment was left on off position. Lab customer was advised of the finished procedure. |
Control of Work Area
Minimum Approach Boundary:
|
Barricade Tape / Attendant:
|
Shock Risk Assessment
System Voltage: 120 Vac
|
Limited Approach Boundary: None
|
Restricted Approach Boundary: None
|
Will the hands enter the RAB: No
|
Voltage Glove Class:
|
Will any other part of the body enter the RAB: No
|
Arc Flash Risk Assessment
Incident Energy: n/a cal/cm2
|
Arc Flash Boundary: n/a
|
Working Distance: No Arc Flash Hazard Present
|
Arc Flash PPE Level: Minimum PPE for Electrical Work
|
Incident Energy Reduction Measures:
|
Capacitor Hazards
Capacitor Bus Voltage:
|
Capacitor total stored energy (joules):
|
Discharge wait time (minutes):
|
Emergency Response Plan
Nearest Landline Location: n/a
|
Emergency Number to Call: (510) 486-6999
|
Sufficient cell phone signal? Yes
|
Clear exit path? Yes
|
AED Location: n/a
|
Fire Extinguisher Location: Located on other side of concrete column.
|
Contact release method available and tested:
|
Environmental Conditions
Does the environment present additional hazards that should be addressed?
None |
Error Precursors
Task Demands:
|
Work Environment:
|
Individual Capabilities:
|
Human Nature:
|
Error Precursor Mitigations:
n/a |
PPE Inspections
Safety glasses (ANSI Z87),
Arc-rated clothing (flash suit, daily wear) including face shield, balaclava, hood., Rubber insulating gloves and leather protectors, Non-melting footwear that fully covers the feet, Removal of conductive articles, Insulated tools, Multimeter and other electrical test instruments |
Notes / Other
|
Perform Job Breifing
PIC Conducts the Job Briefing. Cover all the contents of the Job Safety Plan.
A Job Briefing at a minimum must include: