					Time / Date: 7/25/2023 12:43:42				 				
				 | 
				
				 
					JSP ID: 1306				 
				 | 
				
| 
				 
					Scope of Work: Provide LOTO procedure for contractor to change ballast lamp on one of the fume hood.				 				
				 | 
				|
| 
				 
					Work Order: 				 				
				 | 
				
				 
					Building: Bldg. 978/Rm. 4550				 				
				 | 							
				
| 
				 
					Person in Charge: Felipe Sanchez				 				
				 | 
				
				 
					Lead / Supervisor: Other				 
				 | 
				
| 
				 
					Logged Email: fbsanchez@lbl.gov				 				
				 | 
				
				 
					Division: Facilities				 				
				 | 
				
| 
				 
					QEW Level: QEW 1				 				
				 | 
				
				 | 
				
| 
				 
					Modes of Work: Mode 0 - Electrically Safe Work Condition				 				
				 | 
				|
| 
				 
					Second Person Requirement: Not Required				 				
				 | 
				|
| 
				 
					Second Person Identified: 				 				
				 | 
				|
| 
				 
					List Other Participants: 				 				
				 | 
				|
| 
				 
					Affected Persons Notified: N/A				 				
				 | 
				|
| 
				 
					Switching: No Switching Required				 				
				 | 
				
				 
					Panel / Equipment ID: n/a				 
				 | 
				
| 
				 
					System Information Review: 				 				
				 | 
				|
| 
				 
					Control of Hazardous Energy: Simple LOTO				 				
				 | 
				|
| 
				 
					Equipment Condition: 				 				
				 | 
				|
Sequence of Job Steps
| 
				 
					List basic sequence of steps from start to finish. 				
				Cabinet was already shutoff upon arrival. Pulled out plug from outlet, checked voltage =118Vac. Applied LOTO hardware at power plug. Advised TSS technician that he can start troubleshooting. Ballast replaced with brand-new lamp. Technician tested equipment, working fine. Removed LOTO lock, equipment was left on off position. Lab customer was advised of the finished procedure.  | 
				
Control of Work Area
| 
				 
					Minimum Approach Boundary: 				 				
				 | 
				
| 
				 
					Barricade Tape / Attendant: 				 
				 | 
				
Shock Risk Assessment
| 
				 
					System Voltage: 120 Vac				 				
				 | 
				
| 
				 
					Limited Approach Boundary: None				 				
				 | 
				
| 
				 
					Restricted Approach Boundary: None				 				
				 | 
				
| 
				 
					Will the hands enter the RAB: No				 				
				 | 
				
| 
				 
					Voltage Glove Class: 				 				
				 | 
				
| 
				 
					Will any other part of the body enter the RAB: No				 				
				 | 
				
Arc Flash Risk Assessment
| 
				 
					Incident Energy: n/a cal/cm2
				 				
				 | 
				
| 
				 
					Arc Flash Boundary: n/a				 				
				 | 
				
| 
				 
					Working Distance: No Arc Flash Hazard Present				 				
				 | 
				
| 
				 
					Arc Flash PPE Level: Minimum PPE for Electrical Work				 				
				 | 
				
| 
				 
					Incident Energy Reduction Measures: 				 				
				 | 
				
Capacitor Hazards
| 
				 
					Capacitor Bus Voltage: 				 				
				 | 
				
| 
				 
					Capacitor total stored energy (joules): 				 				
				 | 
				
| 
				 
					Discharge wait time (minutes): 				 				
				 | 
				
Emergency Response Plan
| 
				 
					Nearest Landline Location: n/a				 				
				 | 
				
| 
				 
					Emergency Number to Call: (510) 486-6999				 				
				 | 
				
| 
				 
					Sufficient cell phone signal? Yes				 				
				 | 
				
| 
				 
					Clear exit path? Yes				 				
				 | 
				
| 
				 
					AED Location: n/a				 				
				 | 
				
| 
				 
					Fire Extinguisher Location: Located on other side of concrete column.				 				
				 | 
				
| 
				 
					Contact release method available and tested: 				 				
				 | 
				
Environmental Conditions
| 
				 
					Does the environment present additional hazards that should be addressed? 				
				None  | 
				
Error Precursors
| 
				 
					Task Demands: 				 				
				 | 
				
| 
				 
					Work Environment: 				 				
				 | 
				
| 
				 
					Individual Capabilities: 				 				
				 | 
				
| 
				 
					Human Nature: 				 				
				 | 
				
| 
				 
					Error Precursor Mitigations:  				
				n/a  | 
				
PPE Inspections
| 
				 
					Safety glasses (ANSI Z87), 				
				Arc-rated clothing (flash suit, daily wear) including face shield, balaclava, hood., Rubber insulating gloves and leather protectors, Non-melting footwear that fully covers the feet, Removal of conductive articles, Insulated tools, Multimeter and other electrical test instruments  | 
				
Notes / Other
| 
				 | 
				
Perform Job Breifing
| 
				 
					PIC Conducts the Job Briefing. Cover all the contents of the Job Safety Plan.  				
				A Job Briefing at a minimum must include: 
 Rev 2023.08.22.1 Form Content and Feedback Contact: Michael Rose -- mvr@lbl.gov  | 
				