Time / Date: 8/30/2023 11:33:43
|
JSP ID: 1476
|
Scope of Work: Requested by customer to check AC and DC voltages readings for their equipment.
|
|
Work Order: n/a
|
Building: Bldg. # 2
|
Person in Charge: FELIPE SANCHEZ
|
Lead / Supervisor: Other
|
Logged Email: fbsanchez@lbl.gov
|
Division: Other
|
QEW Level: QEW 1
|
|
Modes of Work: Mode 2 - Energized Diagnostics, Testing and Troubleshooting, Visual Inspection
|
|
Second Person Requirement: Not Required
|
|
Second Person Identified:
|
|
List Other Participants: Manufacturer's technician on site including the customer/user.
|
|
Affected Persons Notified: N/A
|
Switching: Hazardous Switching
|
Panel / Equipment ID: n/a
|
System Information Review:
|
|
Control of Hazardous Energy: Exclusive Control of Plug
|
|
Equipment Condition: Properly installed
|
Sequence of Job Steps
List basic sequence of steps from start to finish.
Customer requested to check AC/DC voltages on their equipment, monitored VAC input = 123.3Vac, DC voltages (24Vdc, -15Vdc, +15Vdc) on chamber #3. Frequency = 60Hz. Not much space at the back of equipment. |
Control of Work Area
Minimum Approach Boundary:
|
Barricade Tape / Attendant:
|
Shock Risk Assessment
System Voltage: 120 Vac
|
Limited Approach Boundary: 42 inches
|
Restricted Approach Boundary: 3 feet, 6 inches
|
Will the hands enter the RAB: Yes
|
Voltage Glove Class: 00
|
Will any other part of the body enter the RAB: No
|
Arc Flash Risk Assessment
Incident Energy: n/a cal/cm2
|
Arc Flash Boundary: n/a
|
Working Distance: 36 inches
|
Arc Flash PPE Level: Minimum PPE for Electrical Work
|
Incident Energy Reduction Measures: 00
|
Capacitor Hazards
Capacitor Bus Voltage: n/a
|
Capacitor total stored energy (joules): n/a
|
Discharge wait time (minutes): n/a
|
Emergency Response Plan
Nearest Landline Location: Inside the room.
|
Emergency Number to Call: 510 486-6999
|
Sufficient cell phone signal? Yes
|
Clear exit path? Yes
|
AED Location: Outside of hallway
|
Fire Extinguisher Location: Located at the hallway
|
Contact release method available and tested: Voltage gloves
|
Environmental Conditions
Does the environment present additional hazards that should be addressed?
Insufficient lighting, Confined space, Insufficient/cramped/awkward space, Noisy environment |
Error Precursors
Task Demands:
|
Work Environment:
|
Individual Capabilities:
|
Human Nature:
|
Error Precursor Mitigations:
Cramped space at the back of equipment. |
PPE Inspections
Safety glasses (ANSI Z87),
Arc-rated clothing (flash suit, daily wear) including face shield, balaclava, hood., Rubber insulating gloves and leather protectors, Non-melting footwear that fully covers the feet, Multimeter and other electrical test instruments |
Notes / Other
n/a
|
Perform Job Breifing
PIC Conducts the Job Briefing. Cover all the contents of the Job Safety Plan.
A Job Briefing at a minimum must include: