Time / Date: 9/5/2023 8:13:32
|
JSP ID: 1497
|
|
Scope of Work: Trace and identify all loads from panel 193A
|
|
|
Work Order: W0342001
|
Building: 72
|
|
Person in Charge: Andrew Southward
|
Lead / Supervisor: Cameron, Benjamin
|
|
Logged Email: amsouthward@lbl.gov
|
Division: Facilities
|
|
QEW Level: QEW 2
|
|
|
Modes of Work: Mode 2 - Energized Diagnostics, Testing and Troubleshooting, Visual Inspection
|
|
|
Second Person Requirement: Safety Watch
|
|
|
Second Person Identified: Alma Duran
|
|
|
List Other Participants:
|
|
|
Affected Persons Notified: N/A
|
|
|
Switching: No Switching Required
|
Panel / Equipment ID: 193A
|
|
System Information Review: Panel Schedules, Arc Flash Labels
|
|
|
Control of Hazardous Energy: LOTO Not Required (Mode 2 or 3 only)
|
|
|
Equipment Condition: Properly installed, All doors and covers closed and fully latched, No signs of impending failure, Not energizing equipment for the first time, or after electrical repair
|
|
Sequence of Job Steps
|
List basic sequence of steps from start to finish.
Establish safe work area, access panel 193A, install circuit tracer, go to downstream loads and use receiver to identify signal, remove tracer after loads have been identified |
Control of Work Area
|
Minimum Approach Boundary: 61
|
|
Barricade Tape / Attendant: Danger - Red
|
Shock Risk Assessment
|
System Voltage: 120/208 V ac
|
|
Limited Approach Boundary: 42 inches
|
|
Restricted Approach Boundary: 12 inches
|
|
Will the hands enter the RAB: Yes
|
|
Voltage Glove Class: 0
|
|
Will any other part of the body enter the RAB: No
|
Arc Flash Risk Assessment
|
Incident Energy: 10.8 cal/cm2
|
|
Arc Flash Boundary: 61 “
|
|
Working Distance: 18 inches
|
|
Arc Flash PPE Level: 2+
|
|
Incident Energy Reduction Measures: 0
|
Capacitor Hazards
|
Capacitor Bus Voltage: Na
|
|
Capacitor total stored energy (joules): Na
|
|
Discharge wait time (minutes): Na
|
Emergency Response Plan
|
Nearest Landline Location: 72 first floor
|
|
Emergency Number to Call: 911
|
|
Sufficient cell phone signal? Yes
|
|
Clear exit path? Yes
|
|
AED Location: On hand
|
|
Fire Extinguisher Location: 72 first floor hallway
|
|
Contact release method available and tested: Upstream breaker or switch, Voltage gloves
|
Environmental Conditions
|
Does the environment present additional hazards that should be addressed?
Insufficient/cramped/awkward space |
Error Precursors
|
Task Demands:
|
|
Work Environment:
|
|
Individual Capabilities:
|
|
Human Nature:
|
|
Error Precursor Mitigations:
Na |
PPE Inspections
|
Safety glasses (ANSI Z87),
Arc-rated clothing (flash suit, daily wear) including face shield, balaclava, hood., Hearing protection, Rubber insulating gloves and leather protectors, Non-melting footwear that fully covers the feet, Removal of conductive articles, Insulated tools, Multimeter and other electrical test instruments |
Notes / Other
|
|
Perform Job Breifing
|
PIC Conducts the Job Briefing. Cover all the contents of the Job Safety Plan.