Time / Date: 9/6/2023 13:22:07
|
JSP ID: 1506
|
Scope of Work: TTS technician adjusting airflow inside bio-safety cabinet.
|
|
Work Order: N/A
|
Building: Potter facility, rm.192-C
|
Person in Charge: FELIPE SANCHEZ
|
Lead / Supervisor: Other
|
Logged Email: fbsanchez@lbl.gov
|
Division: Other
|
QEW Level: QEW 1
|
|
Modes of Work: Mode 2 - Energized Diagnostics, Testing and Troubleshooting, Visual Inspection
|
|
Second Person Requirement: Not Required
|
|
Second Person Identified: N/A
|
|
List Other Participants: Julie Zhu
|
|
Affected Persons Notified: N/A
|
Switching: Non-Hazardous Switching
|
Panel / Equipment ID: LBNL code # 6218176
|
System Information Review: LBNL survey record and TSS labels
|
|
Control of Hazardous Energy: LOTO Not Required (Mode 2 or 3 only)
|
|
Equipment Condition: Properly installed
|
Sequence of Job Steps
List basic sequence of steps from start to finish.
Technician is checking and confirmed that the airflow value is too high. He mentioned about damper adjustment for the bio-safety cabinet. He was able to fix and set the target value inside the cabinet at 78 feet per minute (values between 74 fpm and 85 fpm). Tested this airflow values using his test instrument and adjusting the potentiometer inside the front panel until desired value was attained. Input voltage tested at 115Vac. |
Control of Work Area
Minimum Approach Boundary: N/A
|
Barricade Tape / Attendant: Attendant
|
Shock Risk Assessment
System Voltage: 120 Vac
|
Limited Approach Boundary: 42 inches
|
Restricted Approach Boundary: 3 feet, 6 inches
|
Will the hands enter the RAB: Yes
|
Voltage Glove Class: 00
|
Will any other part of the body enter the RAB: No
|
Arc Flash Risk Assessment
Incident Energy: N/A cal/cm2
|
Arc Flash Boundary: N/A
|
Working Distance: 36 inches
|
Arc Flash PPE Level: Minimum PPE for Electrical Work
|
Incident Energy Reduction Measures: 00
|
Capacitor Hazards
Capacitor Bus Voltage: N/A
|
Capacitor total stored energy (joules): N/A
|
Discharge wait time (minutes): N/A
|
Emergency Response Plan
Nearest Landline Location: Located outside of laboratory room
|
Emergency Number to Call: 510 486-6999
|
Sufficient cell phone signal? Yes
|
Clear exit path? Yes
|
AED Location: Outside of room
|
Fire Extinguisher Location: Located inside test room
|
Contact release method available and tested: Voltage gloves
|
Environmental Conditions
Does the environment present additional hazards that should be addressed?
Insufficient lighting, Noisy environment |
Error Precursors
Task Demands:
|
Work Environment:
|
Individual Capabilities:
|
Human Nature:
|
Error Precursor Mitigations:
N/A |
PPE Inspections
Safety glasses (ANSI Z87),
Arc-rated clothing (flash suit, daily wear) including face shield, balaclava, hood., Rubber insulating gloves and leather protectors, Non-melting footwear that fully covers the feet, Insulated tools |
Notes / Other
N/A
|
Perform Job Breifing
PIC Conducts the Job Briefing. Cover all the contents of the Job Safety Plan.
A Job Briefing at a minimum must include:
Rev 2023.08.22.1 Form Content and Feedback Contact: Michael Rose -- mvr@lbl.gov |