Time / Date: 12/19/2023 9:54:39
JSP ID: 1998
Scope of Work: Perform LP-5132
Work Order: W0359920
Building: 66
Person in Charge: Andrew Southward
Lead / Supervisor: Cameron, Benjamin
Logged Email: amsouthward@lbl.gov
Division: Facilities
QEW Level: QEW 2
Modes of Work: Mode 0 - Electrically Safe Work Condition, Mode 1 - LOTO & Zero Voltage Verification
Second Person Requirement: Standby Person
Second Person Identified: Mike Rose
List Other Participants: Kone
Affected Persons Notified: Yes
Switching: Hazardous Switching
Panel / Equipment ID: 66-EL-Disco, 66-EL-001
System Information Review: Panel Schedules, Arc Flash Labels
Control of Hazardous Energy: Complex LOTO (requires LP, CLP, FLP)
Equipment Condition: Properly installed, All doors and covers closed and fully latched, No signs of impending failure, Not energizing equipment for the first time, or after electrical repair

Sequence of Job Steps

List basic sequence of steps from start to finish.

Verify correct isolation points, switch off circuits, ZVV in elevator control panel, when work is complete remove LOTO and energize

Control of Work Area

Minimum Approach Boundary: 59”
Barricade Tape / Attendant:

Shock Risk Assessment

System Voltage: 277/480 V ac
Limited Approach Boundary: 42 inches
Restricted Approach Boundary: 12 inches
Will the hands enter the RAB: Yes
Voltage Glove Class: 0
Will any other part of the body enter the RAB: No

Arc Flash Risk Assessment

Incident Energy: 13.1 at 66-el-001 cal/cm2
Arc Flash Boundary: 59”
Working Distance: 18 inches
Arc Flash PPE Level: 3
Incident Energy Reduction Measures: 0

Capacitor Hazards

Capacitor Bus Voltage: Following lp instructions
Capacitor total stored energy (joules): Following lp instructions
Discharge wait time (minutes): Following lp instructions

Emergency Response Plan

Nearest Landline Location: Elevator room
Emergency Number to Call: 510-486-7911 (911 from Lab Phone)
Sufficient cell phone signal? Yes
Clear exit path? Yes
AED Location: 4th floor hallway
Fire Extinguisher Location: Elevator room
Contact release method available and tested: Voltage gloves

Environmental Conditions

Does the environment present additional hazards that should be addressed?

None

Error Precursors

Task Demands:
Work Environment:
Individual Capabilities:
Human Nature:
Error Precursor Mitigations:

None

PPE Inspections

Safety glasses (ANSI Z87),
Arc-rated clothing (flash suit,
daily wear) including face shield,
balaclava,
hood.,
Hearing protection,
Rubber insulating gloves and leather protectors,
Non-melting footwear that fully covers the feet,
Removal of conductive articles,
Insulated tools,
Multimeter and other electrical test instruments

Notes / Other

Perform Job Breifing

PIC Conducts the Job Briefing. Cover all the contents of the Job Safety Plan.

A Job Briefing at a minimum must include:
  1. Detailed Scope of Work
  2. Shock and arc flash hazards for each task
  3. Controls to mitigate the hazards (procedures, precautions, energy source controls, PPE requirements)
  4. Work area controls (barricades, signs, attendants)
  5. Emergency Response Plan


Rev 2023.08.22.1
Form Content and Feedback Contact: Michael Rose -- mvr@lbl.gov