Time / Date: 1/29/2024 8:59:57
|
JSP ID: 2144
|
Scope of Work: Preform simple loto on a single pole switch to re-land 120 volt control voltage to a chilled water actuator.
|
|
Work Order: W0361037
|
Building: 91U
|
Person in Charge: Sean Legan
|
Lead / Supervisor: Alford, Steve
|
Logged Email: slegan@lbl.gov
|
Division: Facilities
|
QEW Level: QEW 2
|
|
Modes of Work: Mode 1 - LOTO & Zero Voltage Verification
|
|
Second Person Requirement: Not Required
|
|
Second Person Identified: N/A
|
|
List Other Participants: Mike Rose
|
|
Affected Persons Notified: Yes
|
Switching: Non-Hazardous Switching
|
Panel / Equipment ID: TBD
|
System Information Review: Site Review
|
|
Control of Hazardous Energy: Simple LOTO
|
|
Equipment Condition: Properly installed, Properly maintained, All doors and covers closed and fully latched, No signs of impending failure
|
Sequence of Job Steps
List basic sequence of steps from start to finish.
1- Inspect tools and PPE. 2- Verify multimeter is operational and meets requirements. 3- Preform non-hazardous switching and point of loto. 4- Apply lock and challenge. 5- Preform ZVV at actuator location after verification that meter can read a presence of voltage. 6- Begin task of re-wiring field device. 7- Replace cover and bolt closed. 8- Release loto. 9- Test device for operation. |
Control of Work Area
Minimum Approach Boundary: 36
|
Barricade Tape / Attendant: Attendant
|
Shock Risk Assessment
System Voltage: 120 Vac
|
Limited Approach Boundary: None
|
Restricted Approach Boundary: 3 inches
|
Will the hands enter the RAB: Yes
|
Voltage Glove Class: 0
|
Will any other part of the body enter the RAB: No
|
Arc Flash Risk Assessment
Incident Energy: 0 cal/cm2
|
Arc Flash Boundary: N/A
|
Working Distance: No Arc Flash Hazard Present
|
Arc Flash PPE Level: Minimum PPE for Electrical Work
|
Incident Energy Reduction Measures: 0
|
Capacitor Hazards
Capacitor Bus Voltage: N/A
|
Capacitor total stored energy (joules): N/A
|
Discharge wait time (minutes): N/A
|
Emergency Response Plan
Nearest Landline Location: 91
|
Emergency Number to Call: 15104866999
|
Sufficient cell phone signal? Yes
|
Clear exit path? Yes
|
AED Location: 91U
|
Fire Extinguisher Location: 91U
|
Contact release method available and tested: Upstream breaker or switch
|
Environmental Conditions
Does the environment present additional hazards that should be addressed?
Insufficient lighting, Insufficient/cramped/awkward space, Noisy environment |
Error Precursors
Task Demands:
|
Work Environment:
|
Individual Capabilities:
|
Human Nature:
|
Error Precursor Mitigations:
Have not preformed simple loto in quite some time |
PPE Inspections
Safety glasses (ANSI Z87),
Arc-rated clothing (flash suit, daily wear) including face shield, balaclava, hood., Hearing protection, Rubber insulating gloves and leather protectors, Non-melting footwear that fully covers the feet, Removal of conductive articles, Insulated tools, Multimeter and other electrical test instruments |
Notes / Other
|
Perform Job Breifing
PIC Conducts the Job Briefing. Cover all the contents of the Job Safety Plan.