Time / Date: 9/26/2022 8:14:23
|
JSP ID: 22
|
Scope of Work: Troubleshooting cause of tripped breaker on Xeal car charging unit
|
|
Work Order: 296613
|
Building:
|
Person in Charge: Chris Nelson
|
Lead / Supervisor: Secheck, Stephen
|
Logged Email: gcn@lbl.gov
|
Division: Facilities
|
QEW Level: QEW 2
|
|
Modes of Work: Mode 0 - Electrically Safe Work Condition
|
|
Second Person Requirement: Not Required
|
|
Second Person Identified:
|
|
List Other Participants: Greg Neidiger
|
|
Affected Persons Notified:
|
Switching: Non-Hazardous Switching
|
Panel / Equipment ID: 95A22A-1
|
System Information Review: Panel Schedules, Arc Flash Labels, Clipper Creek User Manual
|
|
Control of Hazardous Energy: Simple LOTO
|
|
Equipment Condition:
|
Sequence of Job Steps
List basic sequence of steps from start to finish.
|
Control of Work Area
Minimum Approach Boundary:
|
Barricade Tape / Attendant:
|
Shock Risk Assessment
System Voltage: 120/208 V ac
|
Limited Approach Boundary: 42 inches
|
Restricted Approach Boundary: 3 inches
|
Will the hands enter the RAB: No
|
Voltage Glove Class: 0
|
Will any other part of the body enter the RAB: No
|
Arc Flash Risk Assessment
Incident Energy: 22.4 @ 18in. cal/cm2
|
Arc Flash Boundary: 107in.
|
Working Distance: 36 inches
|
Arc Flash PPE Level: 4
|
Incident Energy Reduction Measures: 0
|
Capacitor Hazards
Capacitor Bus Voltage:
|
Capacitor total stored energy (joules):
|
Discharge wait time (minutes):
|
Emergency Response Plan
Nearest Landline Location: Rm 101B
|
Emergency Number to Call: 911
|
Sufficient cell phone signal? Yes
|
Clear exit path? No
|
AED Location: 2nd Floor Main Lobby
|
Fire Extinguisher Location: Back of 201 high area
|
Contact release method available and tested: Upstream breaker or switch
|
Environmental Conditions
Does the environment present additional hazards that should be addressed?
None |
Error Precursors
Task Demands:
|
Work Environment:
|
Individual Capabilities:
|
Human Nature:
|
Error Precursor Mitigations:
none |
PPE Inspections
|
Notes / Other
|
Perform Job Breifing
PIC Conducts the Job Briefing. Cover all the contents of the Job Safety Plan.
A Job Briefing at a minimum must include:
Rev 2023.08.22.1 Form Content and Feedback Contact: Michael Rose -- mvr@lbl.gov |