Time / Date: 11/30/2022 8:14:28
|
JSP ID: 280
|
Scope of Work: Apply Arc Flash Label To Disconnect Switch Disconnect Off Wearing proper PPE ZVV LOTO and Remove Seal Tight Load to Transformer Safe of Conductors in a Box. ZVV Transformer Remove Load From Transformer Completely Remove All Electrical Hazards From The Equipment. Leave Disconnect In the Open position with and Admin Lock
|
|
Work Order: 300975
|
Building:
|
Person in Charge: Christopher Nelson
|
Lead / Supervisor: Secheck, Stephen
|
Logged Email: cnelson@lbl.gov
|
Division: Facilities
|
QEW Level: QEW 2
|
|
Modes of Work: Mode 1 - LOTO & Zero Voltage Verification
|
|
Second Person Requirement: Standby Person
|
|
Second Person Identified: Alex Lopez
|
|
List Other Participants:
|
|
Affected Persons Notified: Yes
|
Switching: Hazardous Switching
|
Panel / Equipment ID: 237A1A5A - Nano Writer Disconnect
|
System Information Review: Single Line Drawing, Arc Flash Labels
|
|
Control of Hazardous Energy: Simple LOTO
|
|
Equipment Condition: Properly installed, Properly maintained, All doors and covers closed and fully latched, No signs of impending failure, Not energizing equipment for the first time, or after electrical repair
|
Sequence of Job Steps
List basic sequence of steps from start to finish.
Apply Arc Flash Label. Complete JSP Switch LOTO ZVV Remove Load From Disconnect. Open Transformer and ZVV line And Load. Isolate The Transformer From The Equipment. When It Is In An Electrically safe Condition Release LOTO and Apply a Blue Admin Lock |
Control of Work Area
Minimum Approach Boundary: 42 Inches
|
Barricade Tape / Attendant: Warning - Orange
|
Shock Risk Assessment
System Voltage: 277/480 V ac
|
Limited Approach Boundary: 42 inches
|
Restricted Approach Boundary: 12 inches
|
Will the hands enter the RAB: Yes
|
Voltage Glove Class: 0
|
Will any other part of the body enter the RAB: No
|
Arc Flash Risk Assessment
Incident Energy: 5.83 cal/cm^2 cal/cm2
|
Arc Flash Boundary: 39 inches
|
Working Distance: 18 inches
|
Arc Flash PPE Level: 2
|
Incident Energy Reduction Measures: 0
|
Capacitor Hazards
Capacitor Bus Voltage: NA
|
Capacitor total stored energy (joules): NA
|
Discharge wait time (minutes): NA
|
Emergency Response Plan
Nearest Landline Location:
|
Emergency Number to Call: 911
|
Sufficient cell phone signal? Yes
|
Clear exit path? Yes
|
AED Location: 1st floor lobby 100+ft away
|
Fire Extinguisher Location: Outside room 10ft
|
Contact release method available and tested: Voltage gloves
|
Environmental Conditions
Does the environment present additional hazards that should be addressed?
Insufficient/cramped/awkward space |
Error Precursors
Task Demands:
|
Work Environment: Distractions/interruptions, Unexpected equipment conditions
|
Individual Capabilities:
|
Human Nature: Stress (limits attention)
|
Error Precursor Mitigations:
Don’t be stressed keep the task at hand don’t get distracted be aware of any equipment changes while completing the task |
PPE Inspections
|
Notes / Other
|
Perform Job Breifing
PIC Conducts the Job Briefing. Cover all the contents of the Job Safety Plan.
A Job Briefing at a minimum must include: