Time / Date: 10/3/2024 14:05:38
|
JSP ID: 2990
|
Scope of Work: To produce electrical safe condition to perform maintenance on the VENUS Ion Source chamber, puller electrode and waveguide assembly.
|
|
Work Order: N/A
|
Building: 88
|
Person in Charge: Brendan Ford
|
Lead / Supervisor: Other
|
Logged Email: bpford@lbl.gov
|
Division: Other
|
QEW Level: QEW 2
|
|
Modes of Work: Mode 0 - Electrically Safe Work Condition
|
|
Second Person Requirement: Not Required
|
|
Second Person Identified: N/A
|
|
List Other Participants:
|
|
Affected Persons Notified: Yes
|
Switching: Hazardous Switching
|
Panel / Equipment ID: VENUS Ion Source
|
System Information Review: VENUS Ion Source Chamber & Puller Access Equipment Specific LOTO E6A-1
|
|
Control of Hazardous Energy: Complex LOTO w/ RI
|
|
Equipment Condition: Properly installed, Properly maintained, All doors and covers closed and fully latched, No signs of impending failure, Not energizing equipment for the first time, or after electrical repair
|
Sequence of Job Steps
List basic sequence of steps from start to finish.
-Perform briefing to all LOTO Affected Persons. -Notify Source Operator of intent to apply VENUS Ion Source Chamber & Puller Access LOTO. -Equipment Shutdown: -Have the source operator perform a normal shutdown of the VENUS Ion Source. -Verify VENUS Ion Source is off.. -High-voltage is OFF at VENUS PLC. -28 GHz Gyrotron is OFF at VENUS PLC, OFF at 28 GHz panel. -2X 18 GHz Klystrons are OFF at VENUS PLC, OFF at 18 GHz panel V04. -Hot Rack is OFF. -Note: Verification in following steps is performed at VENUS PLC Menu K2, soft key F6, F7. -Magnet power supplies are OFF. -Magnet currents have gone to ZERO. -40kV 30mA Extraction HVPS U610 Power Plug (Lockout 320) **Turn-on Test -25kV 20mA Puller HVPS U0613 Power Plug (Lockout 320) **Turn-on Test -5kV 24mA Sputter Probe HVPS U07 Sputter Probe PS Power Plug **Turn-on Test -1kV 60mA Bias Disk PS U07 Bias Disk PS Power Plug **PS Output U0718 -RF(CPI 28GHz Xmtr.Main Pwr.) 80A4A6A CB-15 (480VAC, 125A) **Turn-on Test -RF(2X CPI 18GHz Xmtr. Main Pwr.) V04 CB1and CB2 (208V, 30A) **Turn-on Test -Apply ground hook to VENUS chamber. -Apply ground hook to Hot Rack. -Apply ground hook to Puller, if exposed. -Turn off cooling water, as needed. |
Control of Work Area
Minimum Approach Boundary: 60 inches
|
Barricade Tape / Attendant:
|
Shock Risk Assessment
System Voltage: 40kV 30mA, 25kV 20mA, 5kV 24mA, 1kV 60mA, RF 28GHz, 2X RF 18GHz.
|
Limited Approach Boundary: 96 inches
|
Restricted Approach Boundary: 33 inches
|
Will the hands enter the RAB: Yes
|
Voltage Glove Class: 0
|
Will any other part of the body enter the RAB: No
|
Arc Flash Risk Assessment
Incident Energy: 5.3 cal/cm2 cal/cm2
|
Arc Flash Boundary: 41 inches
|
Working Distance: 18 inches
|
Arc Flash PPE Level: 2
|
Incident Energy Reduction Measures: 0
|
Capacitor Hazards
Capacitor Bus Voltage: N/A
|
Capacitor total stored energy (joules): N/A
|
Discharge wait time (minutes): N/A
|
Emergency Response Plan
Nearest Landline Location: 25 feet to the west on the VENUS control console
|
Emergency Number to Call: 911
|
Sufficient cell phone signal? Yes
|
Clear exit path? No
|
AED Location: Will be brought up from the 88" EM Shop to location.
|
Fire Extinguisher Location: 25 feet to the South West
|
Contact release method available and tested: Rescue hook, Voltage gloves
|
Environmental Conditions
Does the environment present additional hazards that should be addressed?
Confined area around panel 80A4A6A. |
Error Precursors
Task Demands:
|
Work Environment:
|
Individual Capabilities:
|
Human Nature:
|
Error Precursor Mitigations:
N/A |
PPE Inspections
Safety glasses (ANSI Z87),
Arc-rated clothing (flash suit, daily wear) including face shield, balaclava, hood., Hearing protection, Rubber insulating gloves and leather protectors, Non-melting footwear that fully covers the feet, Removal of conductive articles, Insulated tools, Multimeter and other electrical test instruments |
Notes / Other
Requirements: Qualified electrical worker (QEW2) trained for testing, switching, and trained in LBNL LOTO , trained in 88” specific LOTO (88-OPS-PRO-017), and authorized.
|
Perform Job Breifing
PIC Conducts the Job Briefing. Cover all the contents of the Job Safety Plan.
A Job Briefing at a minimum must include:
Rev 2023.08.22.1 Form Content and Feedback Contact: Michael Rose -- mvr@lbl.gov |