Time / Date: 9/29/2025 12:02:24
|
JSP ID: 4150
|
Scope of Work: Removing the "AECR Extraction P.S. Remote Control" Chassis.
|
|
Work Order:
|
Building: 88 Cyclotron
|
Person in Charge: Patrick Coleman
|
Lead / Supervisor: Other
|
Logged Email: pcoleman@lbl.gov
|
Division: Other
|
QEW Level: QEW 1
|
|
Modes of Work: Mode 0 - Electrically Safe Work Condition, Mode 1 - LOTO & Zero Voltage Verification
|
|
Second Person Requirement: Not Required
|
|
Second Person Identified:
|
|
List Other Participants:
|
|
Affected Persons Notified: Yes
|
Switching: No Switching Required
|
Panel / Equipment ID: Rack L09 and U03 at the AECR control panel.
|
System Information Review: Drawings 22W5233 and 22W5244 should be reviewed if not already familiar with this chassis.
|
|
Control of Hazardous Energy: Cord & Plug LOTO
|
|
Equipment Condition: Properly installed, Properly maintained, All doors and covers closed and fully latched, No signs of impending failure, Not energizing equipment for the first time, or after electrical repair
|
Sequence of Job Steps
List basic sequence of steps from start to finish.
Receive approval from source operators for work, Inform Cyclotron OIC work is about to begin and AECR will be out of service. LOTO two 120VAC IEC receptacles on two power supplies. Remove chassis. |
Control of Work Area
Minimum Approach Boundary:
|
Barricade Tape / Attendant: Attendant
|
Shock Risk Assessment
System Voltage: 120 Vac
|
Limited Approach Boundary: None
|
Restricted Approach Boundary: 3 inches
|
Will the hands enter the RAB: No
|
Voltage Glove Class: Not Required
|
Will any other part of the body enter the RAB: No
|
Arc Flash Risk Assessment
Incident Energy: None cal/cm2
|
Arc Flash Boundary: None
|
Working Distance: No Arc Flash Hazard Present
|
Arc Flash PPE Level: Minimum PPE for Electrical Work
|
Incident Energy Reduction Measures: Not Required
|
Capacitor Hazards
Capacitor Bus Voltage:
|
Capacitor total stored energy (joules):
|
Discharge wait time (minutes):
|
Emergency Response Plan
Nearest Landline Location: At the AECR control panel
|
Emergency Number to Call: 911
|
Sufficient cell phone signal? Yes
|
Clear exit path? Yes
|
AED Location: Cyclotron control room
|
Fire Extinguisher Location: Top of stairs
|
Contact release method available and tested:
|
Environmental Conditions
Does the environment present additional hazards that should be addressed?
Lookalike equipment |
Error Precursors
Task Demands:
|
Work Environment:
|
Individual Capabilities:
|
Human Nature:
|
Error Precursor Mitigations:
Similar equipment, look for labels. |
PPE Inspections
Safety glasses (ANSI Z87),
Non-melting footwear that fully covers the feet, Removal of conductive articles |
Notes / Other
|
Perform Job Breifing
PIC Conducts the Job Briefing. Cover all the contents of the Job Safety Plan.
A Job Briefing at a minimum must include:
Rev 2023.08.22.1 Form Content and Feedback Contact: Michael Rose -- mvr@lbl.gov |