Time / Date: 1/23/2023 11:09:21
|
JSP ID: 488
|
Scope of Work: Reset breaker
|
|
Work Order: WO307186
|
Building:
|
Person in Charge: Balbino
|
Lead / Supervisor: Keusch, Justen
|
Logged Email: bmmercadal@lbl.gov
|
Division: Facilities
|
QEW Level: QEW 2
|
|
Modes of Work: Mode 1 - LOTO & Zero Voltage Verification
|
|
Second Person Requirement: Not Required
|
|
Second Person Identified: None
|
|
List Other Participants: N/A
|
|
Affected Persons Notified: Yes
|
Switching: Non-Hazardous Switching
|
Panel / Equipment ID: 90A1A
|
System Information Review: Panel Schedules
|
|
Control of Hazardous Energy: Simple LOTO
|
|
Equipment Condition: Properly installed, Properly maintained, All doors and covers closed and fully latched, No signs of impending failure, Not energizing equipment for the first time, or after electrical repair
|
Sequence of Job Steps
List basic sequence of steps from start to finish.
Find the right panel, check the schedule panel, bring out pocket guide follow procedure.use PPE for switching safety glasses and leather gloves, non melting clothing.etc. Reset circuit breaker 21 it close but it slowly trip. Am requesting for Fatse 1 to replace defective circuit breaker for corridor emergency lighting in 2 nd floor. |
Control of Work Area
Minimum Approach Boundary: 12 in
|
Barricade Tape / Attendant: Notice - Blue
|
Shock Risk Assessment
System Voltage: 277/480 V ac
|
Limited Approach Boundary: 42 inches
|
Restricted Approach Boundary: 12 inches
|
Will the hands enter the RAB: No
|
Voltage Glove Class: 0
|
Will any other part of the body enter the RAB: No
|
Arc Flash Risk Assessment
Incident Energy: 0.14 cal/cm2
|
Arc Flash Boundary: 5 in
|
Working Distance: 18 inches
|
Arc Flash PPE Level: Minimum PPE for Electrical Work
|
Incident Energy Reduction Measures: 0
|
Capacitor Hazards
Capacitor Bus Voltage: N/A
|
Capacitor total stored energy (joules): N/A
|
Discharge wait time (minutes): N/A
|
Emergency Response Plan
Nearest Landline Location: Cell phone
|
Emergency Number to Call: 510-486-7111
|
Sufficient cell phone signal? Yes
|
Clear exit path? Yes
|
AED Location: Main lobby 1st floor
|
Fire Extinguisher Location: 1sr floor main lobby
|
Contact release method available and tested: Voltage gloves
|
Environmental Conditions
Does the environment present additional hazards that should be addressed?
None |
Error Precursors
Task Demands:
|
Work Environment:
|
Individual Capabilities:
|
Human Nature:
|
Error Precursor Mitigations:
N/A |
PPE Inspections
|
Notes / Other
None
|
Perform Job Breifing
PIC Conducts the Job Briefing. Cover all the contents of the Job Safety Plan.